experiments is performed, enough equations can be written to compute the
airflows through the various measured parts for each pressure step.
For that purpose, the pressure steps should be the same in each experiment,
for example, 10, 30, 50 and 70 Pa. In order to get accurate pressure steps, the
fans speeds are automatically controlled. Since even this control cannot be
good enough to get accurate measurements (because of external and random
influences such as temperature or wind fluctuations), the data should be auto-
matically selected and recorded only when the following conditions are
fulfilled:
.
The pressure in the room is equal, within a predefined tolerance, to the
predefined value of the pressure for each step.
.
The pressure difference between the room and the guarding zone is smaller
(in absolute value) than a predefined small value.
Finally, for each pressure step and each configuration, several values are meas-
ured and averaged to minimize the effect of ra ndom nois e.
Determining the leakage coefficients
Density corrections
It is the airflow through the fan, q
m
, which is measured and the airflow q
through the leak that is needed to calculate the leakage coefficients. In pressur-
ization experiment s, the air blown by the fan comes from outside while the air
leakage comes from inside. In depressurization experiments, the opposite is the
case, but in both cases the temperature of the airflows may not be the same.
During the measurements, the mass of air is conserved and:
m
q
m
¼ q hence q ¼
m
q
m
ð4:4Þ
where
m
and are the densities of the air going respectively through the fan
and through the leaks. Since the density of the air is inversely proportional to
Figure 4.3 Principle of the guarded zone technique applied to several
walls of a room
Note: At the left, only the external wall is measured, while at the right, the right partition
wall is included in the measurement.
Airtightness 63