Sharp JX-9400 Informations techniques Page 42

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 211
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 41
In principle, the method described above in ‘Tracer gas dilution’ can be
applied to each branch of a duct network. However, this requires as many
tracer gas injections and air sampling measurements as there are airflow
rates. Experience has shown that the experiment can be made simpler, as
shown in Figure 2.5, where most practical and efficient injection locations are
indicated by arrows. In this figure, air samp ling points for the required
tracer gas concentration measurements are also shown.
If several tracer gases are needed but not available, it is possible to use the
same tracer gas in several experiments, injecting the tracer successively at
different locations. In this case, care should be taken to ensure constant airflow
rates in the system. In particular, frequency controllers of the fans should be
blocked at a constant frequency. It is also recommended to start with injection
at location 2, then 3 and finally 1. This strategy shortens the time required
between two experiments to reduce the tracer gas concentration in the
system to a negligible level.
Two tracer gases or two successive measurements with one tracer gas allow
in most cases assessment of all primary and most seconda ry airflow rates:
.
tracer one injected in the main return air duct;
.
tracer two (or a second run with tracer one) injected in the outside air duct.
Additional injection ports may be useful to increase the accuracy. These are:
.
tracer three (or a third run with tracer one) injected in the main supply air
duct, allowing the direct and more accurate determination of supply airflow
rate;
.
tracer four (or a fo urth run with tracer one) injected in the control room at
constant concentration to det ermine leakage from the control room into
the air handling unit.
The optimal tracer gas injection rate depends on the design airflow rate Q
o
in
the duct and on the required concentration, C, itself depending on the sensi-
tivity of the tracer gas analyser. A good method is to adjust the tracer gas
injection flow rate on the basis of the outdoor airflow rate Q
01
.IfC
k
is the
4
3
2
1
C6
C0
C1
C1'
C2 C3
C3'
C4
C4'
C5
C7
Figure 2.5 Locations of tracer gas injection (arrows), and sampling points for
concentration measurements (C
i
) in a typical supply and exhaust air handling unit.
Source: Roulet et al., 1999.
Airflow Rates in Air Handling Units 21
Vue de la page 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 210 211

Commentaires sur ces manuels

Pas de commentaire