Ducts
The duct material and the manufacturing process has the biggest effect on the
perceived air quality (Bjo
¨
rkroth et al., 2000). Depending on the machinery used
in the manufacturing process, new spiral wound ducts, flexib le ducts and other
components of the ductwork might contain small residual amounts of pro-
cessing oil. The oil layer is very thin and invisible, but it emits an annoying
odour. Aluminium ducts score the best with respect to perceived air quality.
Plastic ducts seem a feasible solution, but some flexible plastic ducts are very
smelly.
Oil residu es are the dominating sensory pollution source in new ducts.
The sensory assessments showed a clear correlation between the total mass of
oil residues (average surface density surface area) and the perceived air
pollution (see Figure 6.2).
0
2
4
6
8
10
12
14
16
0 500 1000 1500
Airflow rate [m
3
/h]
Odour intensity
Cassette
Cellulose
Glass fibre
Figure 6.1 Olfactive pollution of various new filters as a function of
airflow rate
Source: Bluyssen et al., 2000a, 2003.
0
1
2
3
4
5
6
7
0.0 0.5 1.0 1.5
Odour intensity
Mass of oil residue in duct [g]
1 m/s
3 m/s
5 m/s
Figure 6.2 Correlation between odour intensity and the mass of
oil residues in the tested ducts
Source: Bjo
¨
rkroth et al., 2000.
Contaminants in Air Handling Units 109