Measured airflow rates differ from the design values in many ventilation
systems. Figure 0.2 shows the relative differences between measured and
design outdoor airflow rate in 37 air handling units, i.e.:
Measured airflow rate design airflow rate
Design airflow rate
These biases range from 79 per cent to þ67 per cent. Only 11 units are within
the 10 per cent range.
Recirculation rates
Some recirculation of air is often planned to di stribute heat or cold without
conditioning too much outdoor air. This, however, decreases the global
indoor air quality, since the contaminants generated within the building are
recirculated throughout the whole building. Therefore, recirculation may not
be desirable. In any case, recirculation should be controlled. Design and
0
50
100
150
200
250
300
0 100 200 300
Design airflow rate [m
3
/(h · person)]
Measured [m
3
/(h · p)]
Figure 0.1 Design and measured outdoor airflow rate per person in
12 buildings
Source: Roulet et al., 1999.
-100%
Percent bias
-50%
0%
50%
100%
Figure 0.2 Relative difference between measured and design outdoor
airflow rate in 37 air handling units
Source: Roulet et al., 1999.
Introduction xv