Sharp JX-9400 Informations techniques

Naviguer en ligne ou télécharger Informations techniques pour Imprimer et scanner Sharp JX-9400. Sharp JX-9400 Technical information Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 211
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs

Résumé du contenu

Page 2

5.10 Global heat recovery efficiency versus nominal heat exchangereffectiveness measured in several units 965.11 Seasonal average coefficient of performanc

Page 3

indoor air quality at a lower energy cost. Once again, measurements may help incommissioning and diagnosing failures.Energy in air handling unitsEnerg

Page 4 - Claude-Alain Roulet

Figure 5.1, a psychrometric chart for air, shows several characteristics ofhumid air. The curves show the water content of air as a function of itstem

Page 5

Figure 5.2 illustrates the paths of temperature and water content of air forheating and humidifying outdoor air in winter, at 08C and 80 per cent rela

Page 6 - Contents

slowly if the air is in contact with massive structures that were cooled downbefore, for example, by strong airing during the cool night.Mechanical co

Page 7

.From the indoor env ironment, heat loads and solar gains. This way ,common in tropical climates, saves the investment of the heating system,and heati

Page 8 - List of Figures and Tables

To improve energy efficiency, mechanical ventilation systems are oftenequipped with heat recovery for recovering the heat contained in exhaust air.This

Page 9

can be transferred from the warm side to the other. The heat recovery efficie ncyof these exchangers ranges from 60 to 80 per cent, depending on the typ

Page 10 - List of Figures and Tables ix

Placing both fans on the same side results in a large pressure differentialthrough the rotating heat exc hanger, thus increasing leaks. A parasiticreci

Page 11

The enthalpy flow, H, is the product of mass airflow rate and specificenthalpy, h:H ¼ Qh ð5:5Þwhere  is the density of air.At ambient temperature, a nu

Page 12 - List of Figures and Tables xi

Leakage through heat exchangersSome heat exchangers let some air leak between both air channels. This is inmost cases not expected, since there are ve

Page 13 - Preamble

7.4 Student distribution for 1, 2 and 5 degrees of freedom comparedto the normal distribution 1587.5 Confidence limit divided by standard deviation ver

Page 14 - Introduction

rates. If these pressure differentials are significantly larger than the nominalvalues, the wheel should be cleaned.Indication on how to measure pressur

Page 15 - Outdoor airflow rate

In simplified methods to calculate heating (or cooling) demand of buildings,ventilation heat loss, V, is often calculated by (CEN, 1999, 2007):V¼_mmð

Page 16 - Recirculation rates

We have mentioned abo ve the following recirculation rates:External Re¼_mmi_mmo_mme¼_mme_mma_mmeð5:20ÞInlet to exhaust Rie¼_mmi_mmrs_mmi¼_mme_mmre

Page 17 - Exfiltration

where:x¼_mmx_mmxþ_mmexfð5:32Þis the extraction efficiency, i.e. that part of the air leaving the ventilated volume,which is extr acted through the air

Page 18 - Ventilation efficiency

which depend s on all parasitic airflow rates. When there is no external recircu-lation (Re¼ 0), Equation 5.37 simplifies to:G¼ð1  exfÞð1  RxsÞ1  R

Page 19

Net energy saving and performance indexHeat recovery systems recover thermal energy but use electric energy for thefans. The net energy saving should

Page 20 - Energy efficiency

Table 5.2 Measured airflow rates with experimental uncertainty band (whenavailable), total and specific fan power in audited unitsAirflow rates (m3/h) Fa

Page 21 - Common techniques

in the three small units, and external recirculation above 20 per cent ismeasured in three large units. These leakages significantly affect heat recover

Page 22 - Airflow Rates in Buildings

Best net ene rgy savings in large units (7 and 8 in Table 5.2) are 80,000–90,000 kWh per winter season, but unit 10 actually wastes as much energy.Sma

Page 23

where: is the density of air,c is the heat capacity of air, is the temperature difference between exhaust air and supply air.The kinetic ene rgy giv

Page 24 - Constant injection rate

6.6 VOC transfer rate in the experiments performed in both EPFLunits (%) 1236.7 VOC transfer rate in the EMPA experiments 1236.8 General IAQ strategie

Page 25 - Pulse injection

consumption of electrical energy by the fan motor, and on the other hand thekinetic energy given to the air in duct.The fan efficiency is the ratio of u

Page 26 - Airflow Rates in Buildings 5

The two ports of this manometer are connected to pressure taps located onboth sides of the fan (see Figure 5.13). Care should be taken to avoid too mu

Page 27

simultaneously the r.m.s. voltage, U, between phase and neutral point, ther.m.s. current, I, running into each motor coil and the phase shift, ’, betw

Page 28 - Airflow Rates in Buildings 7

on which the frequency, the voltage, the current and the fan motor power canbe displayed.Examples of applicationFan efficiencies were measured on severa

Page 29 - Global system of equations

indoor environment quality and health or paying attention to possible damagesto buildings. If a decrease of thermal comfort was implicitly accepted, c

Page 30 - Airflow Rates in Buildings 9

Table 5.4 Uses of energy in buildings, energy saving measures and their effects onindoor environment qualityEnergy use Energy saving measures Impact on

Page 31 - Properties of the flow matrix

For each variant, the effect of the following changes in design and operation wassimulated:.with 50 per cent recirculation instead of no recirculation;

Page 32 - Airflow Rates in Buildings 11

per day), ventilation strategies have a minor influence on heating energy demand.The air may be either heated by coils in the supply air or by radiator

Page 33

a rotating heat exchanger (see Chapter 6, ‘Rotating heat exchangers’), has anegligible effect on energy demand.Infiltration or exfiltration through a lea

Page 34 - Airflow Rates in Buildings 13

6Contaminants inAir Handling UnitsThe purpose of mechanic al ventilation systems is to supply appropriateamounts of clean air and to evacuate vitiated

Page 35

PreambleThis book includes information already published by the author in scientificjournals and in an Air Infiltration and Ventilation Centre (AIVC) te

Page 36 - Airflow Rates

DuctsThe duct material and the manufacturing process has the biggest effect on theperceived air quality (Bjo¨rkroth et al., 2000). Depending on the mac

Page 37 - Source: Roulet et al., 2000a

The effect of airflow on the perceived air quality from ducts was relativelysmall and is probably insignificant in normal applications. Increasing theair

Page 38 - Velocity traverse

Rotating heat exchangersRotating heat exchangers are not themselves sources of contaminants, but theymay transfer contaminants from exhaust to supply

Page 39 - Tracer gas dilution

such that a sector of it that contains exhaust air passes first through the purgingchamber. The author has seen wheels turning the wrong way!In additio

Page 40 - Source: Awbi, 2007

Figure 6.7 shows that certain categories of volatile organic compounds(VOCs) are easily transferred by a sorption transfer mech anism. Among thetested

Page 41 - Tracer gas injection ports

Selecting the panelThe subjects are selected from a group of at least 50 applicants of ages rangingfrom 18 to approximately 35 years old. There is no

Page 42 - Source: Roulet et al., 1999

The 2-propanone gas is evaporated in the PAP by placing one or more 30 mlglass bottles filled with 10 ml of 2-pr opanone and making different holes in t

Page 43

.mechanical air supply with filtered air;.mixing ventilation with a certai n minimum ventilation rate.During the tests, the background level of 2-propa

Page 44 - Node by node method

pollution of concentrations of 2-propanone unknown to them by makingcomparison with the milestones. On the third, fourth and fifth days, traininginclud

Page 45

of Figure 6.10. The concentration of these VOCs in the air is analysed at thefour locations shown in Figure 6.10. Locations C6and C3should be farenoug

Page 46

IntroductionWhy ventilate?Without ventilation, a building’s occupants will initially be troubled by odoursand other possible contaminants and heat. Hu

Page 47

Air sampling and analysisAir at the four locations is sampled with a pump through small tubes filled withan adsorbing medium (for example, activated ch

Page 48 - Eliminating some equations

Wal et al., 1998). These lists can inspire a selection of compounds to include inthe mix. However, the total number of compounds should not be too lar

Page 49 - Simplest way

unit, however, was found with the wheel turning in the wrong way, making thepurging sector inactive.The measured ventilation efficiency in the EMPA acad

Page 50

and rotates at 5 rpm. The diameter of one honeycomb cell is 1.5 mm. The wheelhas no purging sector and the fans are not in their ideal positions. This

Page 51

Results of all experiments are shown in Tables 6.6 and 6.7.Evidence for adsorptionLeakage and entrained air would result in the same recirculation rat

Page 52

experiments, the smallest recirculation rates are for limonene. They are close tothe rates that could be expected from leakage or entrained air.At the

Page 53 - Less than four tracer gases

unity. The average difference between recirculation rates is 22 per cent, close tothe recirculation rate resulting from internal leakage in the EMPA un

Page 54 - Planning tool

.Strategies that affect the design of the HVA C system – design principles andinnovative design strategies.For both of these categories, IAQ strategies

Page 55 - Simple measurement using CO

Table 6.9 Checkpoints in HVAC units in visual inspectionComponent passed failOutdoor chamberAccess door: exists but closed hhChamber is clean (no dirt

Page 56

Table 6.10 IAQ strategies for filtersDesign OperationPrevent filters from becoming a source of pollutionSelect a low-polluting new filterCondition (bake)

Page 57

However, when the outdoor temperature excee ds indoor temperatures, it maybe wise to reduce the ventilation rate, only allowing high levels of ventila

Page 58

Table 6.11 IAQ strategies for ductsDesign OperationPrevent ducts from becoming a source of pollutionUse duct processed withou t oil, and whichdoes not

Page 59

Table 6.12 IAQ strategies for rotating heat exchangersDesign OperationSelect a wheel equipped with purgingsector and install it with the purgingsector

Page 60 - Ventilation Efficiency

Notes1E´cole Polytechnique Fe´de´rale de Lausanne (Swiss Federal Institue of Technology ofLausanne).2 Swiss Federal Research Institute for Materials.T

Page 61 - Air exchange efficiency

7Common Methodsand TechniquesExpressing concentrations and flow ratesCoherent unitsWhen using equations, such as Equation 2.7, to model ventilation sys

Page 62 - Source: Roulet, 2004

withMM ¼PiMiniPinið7:3Þbeing the average molar mass of the mixture. For dry air,MM ¼ 28:96 g/mole.The relative change in density is then:¼MMMM

Page 63 - Measurement method

In a mixture, every gas, x, occupies the whole volume, V:V ¼nxRTpxð7:8ÞThe relations between mass concentration, Cm, molar concentration, CM, andvolum

Page 64

Item 5 is important mainly if the concentration is relatively high (for example,0.1 per cent or higher). For this reason and to achieve also items 3,

Page 65 - Concentration [ppm]

potentially analyse any tracer. Table 7.3 shows their background concentra-tions in outdoor air.It can be seen in Tables 7.2 and 7.4 that no tracer co

Page 66

Mixing tracer gasesPerfect mixing of tracer gas in the air of the measur ed zone or in the measuredduct is essential when determi ning the airflow rate

Page 67

maintained under pressure. It is noted, however, that these two conditionscomplicate the experimental arrangement since control leads must extend toth

Page 68

Measured airflow rates differ from the design values in many ventilationsystems. Figure 0.2 shows the relative differences between measured anddesign out

Page 69 - Source: Roulet et al., 1998

Sampling methodsSamples of air containing tracer gases need to be taken for analysis. There areseveral sampling methods, each one being adapted to a p

Page 70

tight caps. Properly used passive samplers adsorb all the tracers that are in theair enter ing the sampler. They are used to obtain a quantity of trac

Page 71

As an example, for an airflow rate of 100 l/h, that is 28  106m3/s, theminimum pipe inner diameter will be 2.6 mm to have an air speed of 5 m/s.In th

Page 72

Remember, however, that, in order to achieve good mixing, it is advanta-geous to inject the tracer continuously whenever possible. A series of shortpu

Page 73 - The model matrix M

up to several minutes for gas chromatographs or multi-tracer infraredanalysers. Faster analysis will enable more frequent sampling of each zoneand hen

Page 74 - Condition of the model matrix

vapour and CO2present at high concentrations in the air. Filters are used tominimize the effect but humidity should be measured simultaneously tosome t

Page 75 - Factorial designs

this field. Only ions having a charge-to-mass ratio that corresponds to a givenradio frequency reach an orifice at the end of that path and pass into an

Page 76 - 3-D designs

Gas chromatographyA puff of the sampled air is injected into a separating (chromatographic)column, a tube in which adsorbent material is packed. This c

Page 77

By making the prescr ibed number of strokes of the hand-held bellows, thecorrect amount of air is drawn through the tube. This enables the tracer gase

Page 78

Linear least square fit of the first kindSuch methods are used to find the coefficients of leakage models of Equations4.1 or 4.2 in fa n pressurization (se

Page 79

measured recirc ulation rates are compared in Figure 0.3. These are seldom thesame. Even worse: as shown in Figure 0.4, out of 27 units planned withou

Page 80 - Measurement methods

Confidence in the coefficientsThe variances on the linear coefficients of the regression of the first kind areusually estimated using the following relation

Page 81

Regression of the second kindWhen there are uncer tainties in both axes, there is no reason to emphasize the xaxis, and the same procedure can be foll

Page 82 - Reductive sealing

where "yand "xare the experimental errors on y and x respectively anddeduce a corr esponding value of a using Equation 7.16. This recipe doe

Page 83

will be obtained, and a correlation between C and n will be found: the larger Cvalues correspond to the smaller n and vice versa. A good identification

Page 84 - Density corrections

the a posteriori information. T his new distributio n:ðzÞ¼C exp 12fðzÞTC1TðzÞþðz  zpÞTC1zðz  zpÞghið7:41ÞFrom this distribution, the z vector

Page 85 - Two measurement points

Generally, an instrument does not directly give the required information. Inmost cases, several measurements are combined to obtain the needed value.

Page 86 - Airtightness 65

domain. The statistical method allows one to obtain more information on thereliability of the results.Because of rando m reading errors and uncontroll

Page 87

Variance and standard deviationA figure representing the importance of the scattering around the average valueis the mean square deviation or variance:

Page 88 - Airtightness of buildings

The confidence interval [c; c] of the normal distribution is obtained bysolving the equation:P ¼ erfðc=ffiffiffi2pÞð7:57Þfor a given value of P.If the norma

Page 89 - External fan

more detail in statistical tables such as Zwillinger (2003)) and in mostmathematical software packages.Confidence interval of the Gaussian distribution

Page 90 - Leakage visualization

the design and measured exfiltration ratios, i.e. parts of the supply air leakingthrough the building envelope in 30 units.Ventilation efficiencyAn efficie

Page 91 - The stack effect method

Hence, we can state: ¼hxiIcð7:65ÞP is the probability that the confidence interval contains the ‘true’ value. P ischosen a priori, in practice betwee

Page 92 - Airtightness 71

the infinitely small increments dxiby the absolute error xiand by summing theabsolute values:yj¼Xi@fj@xixið7:67ÞIf only arithmetical operati

Page 93 - Neutral height method

represented by a vector x and a matrix A. The question is: which is theresulting error y on the vector y, which is the vector containing the final r

Page 94 - Airtightness 73

the partial derivatives are computed as above and we get finally:s2yi; yj¼Xklmnikyljmyns2aklamnþXklikjls2xkxlþXklmnðikyljm jkylimÞs2aklxmð7:7

Page 95 - Pressurization method

and the matrix norm is subordinated to the vectorial norm jxj if:jAj¼maxjAxjjxjfor any x 6¼ 0 ð7:85ÞThe subordinated norm is the smallest matrix nor

Page 96 - Flow rate difference method

where 1and nare respectively the largest and the smallest eigenvalues ofAHA. This number is the spectral condition number.Constant absolute errorIf

Page 97 - SealSeal

From which, using the method described in Chapter 1, ‘Zone by zonesystems of equations’, we get the airflow rates to and from each zone [m3/h]shown in

Page 98 - Related to Energy Efficiency

ReferencesAeschlimann, J.-M., C. Bonjour and E. Stocker, eds, 1986, Me´thodologie et Techniquesde Plans d’Expe´riences: Cours de Perfectionnement de l

Page 99

Brown, S. K., M. R. Sim, M. J. Abramson and C. N. Gray, 1994, Concentrationsof volatile organic compounds in indoor air: A review, Indoor Air, vol. 4,

Page 100 - Energy in air handling units

Hakajiwa, S. and S. Togari, 1990, Simple test method of evaluating exterior tightnessof tall office buildings, in E. M. H. Sherman, ed., ASTM STP 1067,

Page 101

When assess airflows in buildings?Ventilation performance should be checked early to detect potential problemsand to optimize the overall performance o

Page 102

Presser, K. H. and R. Becker, 1988, Mit Lachgas dem Luftstrom auf der SpurLuftstrommessung in Raumlufttechnischen Anlagen mit Hilfe der Spurgasmethode

Page 103

Sandberg, M. and C. Blomqvist, 1985, A quantitative estimate of the accuracy of tracergas methods for the determination of the ventilation flow rate in

Page 104 - Heat exchangers

Annex AUnit Conversion TablesIntroductionSI units are used throughout this book. Non-SI units are, however, of generaluse in air infiltration and venti

Page 105 - Types of heat exchangers

AreaName Symbol m2cm2sq in sq ft sq yd1 square metre m21 104 1550 10.7639 1.195991 square centimetre cm21041 0.3937008 0.0328084 0.010936131 square i

Page 106 - Rotating heat exchangers

PressureName Symbol Pa mbar mm H2OinH2O psi1 Pascal Pa 1 0.01 0.102 0.004 145.037  1061 millibar mbar 100 1 10.2 0.422 14.5037  1031 mm water colu

Page 107 - Heat exchange efficiency

Annex BGlossaryItems in italics are additional entries in the glossary.Age of the air (or age of a contaminant)Average time period since the fresh air

Page 108

adventitious openings), caused by pressure effects of the wind and/or theeffect of differences in the indoor and outdoor air density.Air infiltration char

Page 109

Building componentGeneral term for any individual part of the building envelope. Usually appliedto doors, windows and walls.Building envelopeThe total

Page 110 - Ventilated

Constant concentration techniqueA method of measuring ventilation rate whereby an automated sy stem injectstracer gas at the rate required to maintain

Page 111 - Global heat recovery efficiency

Distribution effectivenessRatio of the average tracer gas or contaminant concentration to the concentrationthat could be reached, at equilibrium, in th

Page 112

Ventilation and Airflow in Buildings

Page 113

effectiveness of the ventilation in appropriately distributing the air in the venti-lated space or in evacuating contaminants emitted at a given locati

Page 114 - Source: Roulet et al., 2001

Fan pressurizationGeneral term applied to any technique involving the production of a steadystatic pressure differential across a building envelope or

Page 115 - Examples of application

Indoor air pollutionPollution occurring indoors from any source, i.e., from outside as well as insidethe building.Infrared gas analyserInstrument used

Page 116

MixingThe degree of uniformity of distribution of outdoor air or foreign material in abuilding.Mixing fanSmall electric fan used to aid the mixing of

Page 117

Piston-type ventilationSee displacement flow.Pitot tubeAnemometer measuring the difference between the pressure in a tube facingthe flow, in which the flo

Page 118 - Energy for ventilation

Reductive sealing methodA method of determining the leakage of specific building comp onents bypressurizing the building and recording the leakage chan

Page 119

Site analysisApplied to any tracer gas measurement technique where tracer gas concentrationsand air exchange rates are determined directly at the meas

Page 120 - Measurement of airflow rate

Turnover time of a contaminantRatio of the mass of contaminant con tained in an enclosure to the mass flow rateof the contaminant source in this enclos

Page 122

Indexabsolute error, 154active ways, 78adsorption, 123age matrix, 10age of the air, 39, 42, 174airage of, 39, 42, 174changeefficiency, 40leakage rate, 6

Page 123

conductance, 176confidence interval, 28, 149, 154,155conservation equation, 1, 7, 177constant concentration, 3, 12, 176constant injection rate, 3, 12,

Page 124

1995, 2003). This can, however, be avo ided by appropriate design and main-tenance. Chapter 5, ‘Energy effect of IAQ measures’, lists the sources andca

Page 125

air change rate, 67and heat recovery, 89area, 67, 178characteristics, 180coefficients, 60, 64heat exchangers, 88visualization, 69least square fit, 27, 14

Page 126 - Recirculation

tracer gas (Continued)injection, 21mixing of, 137pulse injection, 4, 12, 182sampling, 22techniques, 12trained panel, 113transfer of contaminants, 10un

Page 127 - Heat recovery

1Airflow Rates in BuildingsThis chapter intends to help the reade r to measure airflow rates and air changerates in buildings and room s, independently

Page 128 - Ductwork

outdoor environment is then:dmdt¼ I þ CoQoi CiQioð1:1Þwhere:m is the mass of tracer gas in the zone (kg);I is the injection rate of the tracer gas (k

Page 129 - Air Handling Units

This solution can be simplified, depending on the way the tracer isinjected.Tracer decay, no injectionA suitable quant ity of tracer gas is injected to

Page 130 - Source: Bjo

Constant concentrationUsing an electronic mass flow controller monitored by the tracer gas analyser,the concentration of tracer gas can be maintained c

Page 131 - Humidifiers

Applying again the integral mean value theorem, we get:m ¼ Qs;ið0Þðtf0CðtÞdt with 0 <0< tfð1:20ÞCombining Equations 1.18 and 1.20, we get:Qið

Page 132

concentration C (Ciindoors and Cooutdoors) by:Qe¼SCi Coð1:22Þwhere S is the CO2source strength, i.e. about 20 l/h. The equivalent outdoorairflow rate

Page 133 - Source: Roulet et al., 2000

do not change during the measurement campaign. This section describes waysof interpreting the records of tracer gas injection rates and concentration

Page 134 - Measurement protocols

where:mikis the mass of tracer gas k in zone i;Iikis the injection rate of tracer gas k in (or just upwind of ) zone i;Cjkis the concentration of trac

Page 136 - Source: Bluyssen, 1990

C contains the differences in mass concentrations Cik C0kof gas k in zone i.I is the matrix containing the mass flow rates Iikof the tracer, k , in zon

Page 137 - Training procedure

Properties of the flow matrixThe total outdoor airflow rate to each zone, i, is easily obtained by summing thecolumns of the flow matrix:Qi0¼XNj ¼1Qijð1:

Page 138 - Principle of the method

sums of the  matrix are the mean age of air in the corresponding rooms:hii¼XNj ¼1ijð1:38ÞThis relation enables the measurement of the room mean ag

Page 139 - Injection technique

The air mass conservation (Equat ion 1.23) is rewritten as:q0i¼ TiXNj ¼0qijð1  ijÞTjXNj ¼1qjið1  ijÞþViTidTidtð1:43ÞThese last two systems includ

Page 140 - Ø 6 mm copper tube

.The long-term integral method, generally used with passive sources andsamplers, also gives a biased estimate of the average airflow rate. Since themea

Page 141 - Example of application

.Constant injection used with long-term direct solution is simpler to use andmay give, under certain conditions, unbiased estimates of an average airfl

Page 142

2Airflow Ratesin Air Handling UnitsAir handling units are designed to supply new air to the ventilated zone and toextract vitiated air from this zone.

Page 143

placed in the flow, for example a nozzle, Venturi or sharp-edged orifice (ISO,2003). Alternatively, the air speed can be measured directly at a number o

Page 144 - Evidence for adsorption

 is the reduction ratio, which is the ratio of the smallest diameter to thediameter of the pipe.The flow may be restricted with an orifice plate, a noz

Page 145

from 0.05 to 5 m/s, and are well suited for speeds of 1–5 m/s, which are typical inventilation ducts.Helix anemometers measure the rotation speed of a

Page 146 - HVAC systems

BUILDINGS|ENERGY|SOLAR TECHNOLOGYVentilation and Airflow in BuildingsMethods for Diagnosis and EvaluationClaude-Alain RouletLondon.Sterling, VA

Page 147

Assuming that no trac er is lost in between, the mass balance of the tracer gasis, at steady state:I ¼ðC  C0ÞQ ð2:3Þwhere:C is the tracer concentrati

Page 148

The methods described in the section on ‘Measurement of airflow rate in aduct’ (above) may of course be used to measure the ai rflow rates through grill

Page 149

In principle, the method described above in ‘Tracer gas dilution’ can beapplied to each branch of a duct network. However, this requires as manytracer

Page 150

expected tracer gas concentration of tracer k:Ik¼ CkQ01ð2:5ÞSampling points for concentration measurementsTracer gas concentrations are measured at se

Page 151

bringing additional tracer into the analyser, thus biasing the concentrationmeasurement. To avoid this, use different colours for injection and samplin

Page 152

gas conservation equations can be rearranged so as to obtain one system ofequations per node, giving all airflow rates entering in this node. At steady

Page 153 - Common Methods

recirculated air passes through a leak between extract and supply parts of theair handling unit or through a purpose-installed duct. Alternatively, ve

Page 154

Node 2, return I11¼ðC11 C31ÞQ12þðC61 C31ÞQ62þðC71 C31ÞQ72ð2:10Þ0 ¼ðC12 C32ÞQ12þðC62 C32ÞQ62þðC72 C32ÞQ720 ¼ðC13 C33ÞQ12þðC63 C33ÞQ62þðC73 C3

Page 155 - Properties of tracer gases

This system of 27 equations when combined with the system of Equation 2.9can be solved in various ways to provide the six main airflow rates andpotenti

Page 156

Simplest wayA method providing all airflow rates with the simplest solutions – henceprobably the least sensitive to measurement errors – is given below

Page 157 - Source: Dietz et al., 1983

First published by Earthscan in the UK and USA in 2008Copyright # Claude-Alain Roulet, 2008All rights reservedISBN-13: 978-1-84407-451-8Typesetting by

Page 158 - Mixing tracer gases

withQ46¼ TðP; 1ÞffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiðC402 C42Þ2I252þ I252ðC2402þ C242ÞðC402 C42Þ4sð2:28

Page 159 - Tracer density problem

The bias resulting from the alias with Q72is not taken into account in theconfidence interval. If tracer 4 is used, we get:Leakage to node 2Q72¼ðC32 C

Page 160 - Passive sampling

orQ04ffi Q24ðC3k C4kÞðC4k C0kÞ¼ Q12ðC6k C1kÞðC6k C3kÞðC3k C4kÞðC4k C0kÞð2:41ÞQ04¼TðP; 1ÞðC4k C0kÞ2ffiffiffiffiffiffif04pð2:42Þwheref04¼ðC6k C3kÞ2ðC3k C1kÞ

Page 161 - Networks, pumps and pipes

with k 6¼ 2(k ¼ 4 is not recommended here).Q76¼TðP; 1ÞC7k C6kffiffiffiffiffiffif76pð2:52Þwheref76¼ Q226C23kþ Q246C24kþðQ26þ Q46 Q76Þ2C26kþðC3k C6kÞ2Q226þð

Page 162

Planning toolThere are many types of air handling units, and, from our experience, each newmeasurement poses new problems. It is hence impossible to p

Page 163 - Objective of the analysis

Leaks in the heat exchanger, as well as in the return air channel, weredetected with this measurement. Measurement in three other identical unitsin th

Page 164

concentrations are in volumetric ratios. It is not possible with only one tracerinjected into the ventilated space to differentiate between outdoor air

Page 165 - Mass spectrometry

with ¼nð1  RÞ1  R þ ið2:63ÞThe theoretical exponential can be fitted to the experimental points, as shownin Figure 2.11 depicting an actual experi

Page 166

The recirculation airflow rate can then be calculated using:Q62¼ Q24 Q12ð2:66ÞwithQ62¼ TðP; 1ÞffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiQ224þ Q212qffi TðP ; 1Þffiffiffiffiffiffi

Page 167 - Chemical indicator tubes

withR ¼QQffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffið1 þ RÞpð2:73ÞOr method CR ¼ 1 Q12Q24withR ¼ffiffiffi2pQQð1  RÞð2:74Þassuming that the relative error Q=Q is the same for bo

Page 168 - Identification methods

ContentsList of Figures and Tables viiPreamble xiiIntroduction xiii1 Airflow Rates in Buildings 1Single-zone measurements 1Application to buildings, mu

Page 169

3Age of Air andVentilation EfficiencyThe airflow patterns should, in principle, be organized in order that new airis brought to the head of the occupants

Page 170 - Confidence in the coefficients

However, the more time a small volume of air spends in a room, the more itwill be contaminated by pollutants.Since there is a large number of air part

Page 171 - Orthogonal regression

constant. In rooms with complete mixing, the room mean age of air equalsthe nominal time constant, and the air exchange efficiency is 50 per cent.Short-

Page 172 - Bayesian identification

corresponding to the nominal time constant. The air exchange efficiency inthis very theoretical case is 100 per cent. At 99 per cent air exchange effi-cie

Page 173

assumes that the tracer gas behaves the same as the air: no adsorption andsame buoyancy, which is the case if the tracer concentration is small. It ca

Page 174 - Error analysis

To interpret the recorded tracer gas concentrations and obtain the age ofair, the background (or supply) concentration should first be subtracted froma

Page 175 - A few statistics

The local mean age of air at any location is the integral (or zero moment)of the probability distribution:r¼ 0¼ð10FrðtÞdt ð3:8ÞThe first moment of th

Page 176

where:Fjis the probability distribution at time t ¼ j t,Step-up case Fj¼ 1 Cð t0þ jtÞCð1ÞDecay case Fj¼Cðt0þ j tÞCð t0Þð3:16ÞN is the last measure

Page 177 - Statistical distributions

withFj¼ TðP; 1ÞffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiCeðjt þ t0ÞCeðjt þ t0Þ2þCeðjt þ

Page 178

a displacement ventilation system, as shown in Figure 3.6. The conferenceroom is 8 m by 10 m wide and 3 m high. It is completely embedded in an old,ma

Page 179

Measurement methods 59Determining the leakage coefficients 63Corrections for standard conditions 65Ways of expressing the airtightness 66Airtightness of

Page 180 - Most simple error analysis

efficiency was doubled, and the mean age of air was maintained despite areduction of the ventilation rate – and of energy use – by a factor two.Mapping

Page 181 - Linear equations systems

straightforward, takes time and has its cost, the theory of experimentaldesign (Box et al., 1978) may help in providing a maximum of informationthroug

Page 182

for which seven coefficients must be determined. Table 3.2 summarizes theminimum number of measurements needed.Location of the measurement pointsAn impo

Page 183 - Upper bound of the errors

The criteria described below are used to establish the most efficientdesign.Criteria for location of the measurement pointsThe model matrix MFirst, let

Page 184

If 2is the experimental variance of the measured variable v, the variance2(ve) of the estimated variable is:2ðveÞ¼rTðMTMÞ1r2ð3:36ÞA variance func

Page 185

As mentioned above, the experimental domain is about 20 per centsmaller than the measured space, samples of air being taken at least 0.1 timesthe char

Page 186

can be added to obtain a minimum design for a quadratic model, which has acondition number of 6.3 (see Figure 3.9).The 2-D full factorial design with

Page 187 - References

the points 8, 5 and 2 can be deleted (in that order) giving finally a designhaving 12 points and a condition number of 4.8. Finally, deleting two morep

Page 188

Example of applicationThe age of air was mapped in the conference room after the improvement,first in the empty room, and then with ten occupants sitti

Page 189

4AirtightnessWhy check airtightness?Controlled airflows, having adequate flow rate and passing at the appropriatelocations are essential for good indoor

Page 190

List of Figures and TablesFigures0.1 Design and measured outdoor airflow rate per person in12 buildings xv0.2 Relative difference between measured and d

Page 191

ventilation rate. Maintaining air quality requires an increase in supply air,leading to energy wastage.Checking the airtightness of a building envelop

Page 192 - Unit Conversion Tables

column) and the airflow rate through the fan is measur ed using any of thefollowing methods:.The airflow rate through a fan depends on the pressure diffe

Page 193

Inverting this relationship gives the airflow rate resulting from a pressuredifferential:q ¼b þffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffib2 4app2að4:3ÞBy fitting one of t

Page 194 - Mass flow rate

flow rates at each pressure using the method described in section ‘Determiningthe leakage coefficients’, below.Components that can usually be sealed incl

Page 195 - Glossary

experiments is performed, enough equations can be written to compute theairflows through the various measured parts for each pressure step.For that pur

Page 196 - Glossary 175

its absolute temperature, and as long as the pressure differential remains smallwith respect to the atmospheric pressure:q ¼ qmTTmð4:5Þwhere T and Tmar

Page 197

intervals. If the coefficients a and b are known, the airflow coefficient C and theexponent n are calculated using:C ¼ expðaÞ and n ¼ b ð4:11ÞThe Etheridge

Page 198 - Glossary 177

Using the subscript o for these standard conditions and no subscript for themeasurement conditions, then:Co¼ Coð2n 1Þoð1 nÞð4:15Þwhere  is

Page 199

Virtual air change rateBy dividing the airflow rate at conventional pressure by the internal volume ofthe tested enclosure gives a virtual leakage air

Page 200 - Glossary 179

in order to create a pressure difference large enough to minimize influencesfrom wind and temperature differences on the results. This pressure differen-t

Page 201

3.1 Ventilation modes with typical airflow patterns and airchange efficiencies 413.2 Typical probability density curves for the age of the air 413.3 Typi

Page 202 - Glossary 181

The overall airtightness of the structure and the size of the available fangovern the maximum volume of enclosure that may be pressurized. Even iflarg

Page 203

case, the airtightne ss is not good enough and cold air enters the inhabited spacethrough cracks between wooden panels.The stack effect methodThis simp

Page 204 - Glossary 183

there is a priori only one neutral plane at the height z0. The neutral plane is thegenerally horizontal plane in the building or part of it where the

Page 205

measuring the air speed at several locations and integrating over the wholeopening or using a tracer gas.gQgþ tCtpðztÞnþðznzrbdðrCrpðzrÞnÞ¼0 ð4:2

Page 206 - Glossary 185

top of the opening to observe the flow direction. The neutral level is locatedbetween the ingo ing and outgoing flow directions. Sensitivity can be incr

Page 207

that Ti> To, by:Q ¼ QAToTi1=21 znH3=2znH3=2ffi QAð1  aÞ3=2 a3=2ð4:29Þwith a ¼znHwhere znis the height of the neutral level.The opening area

Page 208

example, using plastic sheeting and adhesive tape. Inflated balloons are alsowell suited to seal circular ducts.Tracer gas injection and air sampling t

Page 209

upstream end of the duct and its concentration is measured at both ends to givethe flow rate at each.The leakage of the whole supply or exhaust network

Page 210

5Measurements and MeasuresRelated to Energy Efficiencyin VentilationEnergy in buildingsEnergy uses and indoor environment qualityEnergy is used in build

Page 211

Passive and active ways to get high quality buildings.Passive ways are architectural and constructive measures that naturally providea better indoor e

Commentaires sur ces manuels

Pas de commentaire