Table 5.2 Measured airflow rates with experimental uncertainty band (when
available), total and specific fan power in audited units
Airflow rates (m
3
/h) Fan power
Unit Outdoor air Supply air Extract air Exhaust air W Wh/m
3
1 1900 100 2070 70 1790 40 1600 200 990 0.27
2 2530 80 2900 200 1860 50 1500 200 850 0.19
3 2380 70 2480 70 1930 40 1830 50 1800 0.42
4 2200 300 3400 100 3240 90 2000 2000 1800 0.33
5 5000 200 5400 100 6000 700 5500 700 3710 0.34
6 15,000 2000 16,400 700 11,000 1000 10,000 3000 11,800 0.45
7 11,000 400 11,600 200 10,000 300 9500 900 8180 0.39
8 16,000 1000 17,400 700 13,400 600 12,000 2000 9760 0.33
9 9000 1000 10,000 2000 1970 90 1000 3000 3800 0.35
10 14,300 600 16,200 400 3420 70 1000 1000 7970 0.45
a 25 36 34 24 13 0.22
b 42 75 74 41 27 0.24
c 74 87 87 74 32 0.20
Table 5.3 Outdoor air efficiency,
o
, exfiltration and infiltration ratios
exf
and
inf;
external and internal recirculation rates R
e
,R
xs
and R
ie
, heat
recovery effectiveness "
HR
, global heat recovery efficiency
G
, specific net
energy saving, SNES in Wh/m
3
, and coefficient of performance, COP, of
audited air handling units
Unit
o
exf
inf
R
e
R
xs
R
ie
x
"
HR
G
SNES COP
1 97% 16% 0% 6% 7% 0% 86% 70% 56% 1.55 6.5
2 92% 47% 9% 20% 5% 0% 59% 70% 39% 1.35 8.0
3 100% 29% 7% 0% 5% 0% 72% 90% 62% 1.18 5.2
4 68% 77% 76% 55% 1% 0% 31% 30% 9% 0.05 3.3
5 98% 8% 17% 0% 7% 0% 92% 80% 69% 1.92 6.7
6 97% 43% 8% 0% 6% 0% 61% 90% 52% 0.69 4.5
7 100% 14% 0% 4% 2% 0% 87% 80% 68% 1.45 5.5
8 97% 25% 0% 0% 0% 0% 77% 70% 54% 1.17 5.5
9 95% 97% 49% 0% 0% 0% 10% 50% 5% 0.37 1.8
10 93% 91% 18% 100% 6% 0% 18% 50% 8% 0.92 1.5
a 74% 8% 0% 0% 33% 0% 94% 63% 40% 1.37 6.2
b 57% 2% 0% 0% 44% 4% 99% 80% 44% 2.21 6.8
c 68% 0% 0% 0% 39% 25% 100% 90% 55% 2.69 8.2