Table 6.14 IAQ strategies for coils
Design Operation
Prevent water reservoirs and material of coils from becoming a source of pollution
Keep outlet of drain free at the lowest
point of the drain pan (include angle)
Water/condensation should not stay too
long in reservoirs: change system design
Remove oil before install ation
Prevent corrosion by selecting the proper
material
Do not place any adsorbing material
behind cooling coil
Maintain on time
Water collection reservoirs: remove
water regularly, clean
Check for visible growth of moulds on coil
surface
Prevent water droplets from being produced
Place a droplet catcher behind cooling coil
Contaminants in Air Handling Units 131