The WAGO-I/O-SYSTEM 750 19
Technical Data
WAGO-I/O-SYSTEM 750
Bus System
Mechanical strength acc. to IEC 61131-2
Test specification Frequency range Limit value
5 Hz f < 9 Hz
1.75 mm amplitude (permanent)
3.5 mm amplitude (short term)
9 Hz f < 150 Hz
0.5 g (permanent)
1 g (short term)
IEC 60068-2-6 vibration
Note on vibration test:
a) Frequency change: max. 1 octave/minute
b) Vibration direction: 3 axes
15 g IEC 60068-2-27 shock
Note on shock test:
a) Type of shock: half sine
b) Shock duration: 11 ms
c) Shock direction: 3x in positive and 3x in negative
direction for each of the three mutually perpendicular axes
of the test specimen
IEC 60068-2-32 free fall 1 m
(module in original packing)
*) QP: Quasi Peak
Note
If the technical data of components differ from the values described here, the
technical data shown in the manuals of the respective components shall be
valid.