Sharp R-580D Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Climatiseurs à système divisé Sharp R-580D. Sharp R-580D User`s manual [en] Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 48
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Cancels: II 580D-90-4 II 580D-90-5
7/15/00
IMPORTANT — READ BEFORE INSTALLING
1. Read and become familiar with these installation in-
structions before installing this unit (Fig. 1).
2. Be sure the installation conforms to all applicable
local and national codes.
3. These instructions contain important information for
the proper maintenance and repair of this equipment.
Retain these instructions for future use.
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . .1,2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-20
I. Locate the Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
II. Unit Duct Connections . . . . . . . . . . . . . . . . . . . . . . . 5
III. Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
IV. Field Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20,21
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21-31
I. Heating Section Start-Up and Adjustments . . . . . 21
II. Cooling Section Start-Up and Adjustments . . . . . 24
III. Indoor Airflow and Airflow Adjustments . . . . . . . . 26
CARE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . .31,32
I. Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32-37
I. Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
II. Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
III. Condenser Fan Adjustment . . . . . . . . . . . . . . . . . . 32
IV. Blower Belt Adjustment . . . . . . . . . . . . . . . . . . . . . 32
V. Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . 33
VI. Main Burners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
VII. Flue Gas Passageways . . . . . . . . . . . . . . . . . . . . . . 36
VIII. Combustion-Air Blower. . . . . . . . . . . . . . . . . . . . . . 36
IX. Limit Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
X. Burner Ignition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
XI. Replacement Parts. . . . . . . . . . . . . . . . . . . . . . . . . . 36
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .38-45
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Recognize safety information. This is the safety-alert sym-
bol ( ). When you see this symbol on the unit and in in-
structions or manuals, be alert to the potential for personal
injury.
Understand the signal words — DANGER, WARNING, and
CAUTION. These words are used with the safety-alert sym-
bol. Danger identifies the most serious hazards which will
result in severe personal injury or death. Warning indicates
a condition that could result in personal injury. Caution is
used to identify unsafe practices which would result in minor
personal injury or product and property damage.
1. The power supply (volts, hertz, and phase) must cor-
respond to that specified on unit rating plate.
2. The electrical supply provided by the utility must be
sufficient to handle load imposed by this unit.
3. Locate connections for gas inlet, electrical inlets, con-
densate drain, duct connections, and required clear-
ances before setting unit in place. Refer to Locate the
Unit section on page 2 and Fig. 2-4 for locations.
WARNING: Improper installation, adjustment,
alteration, service, maintenance, or use can cause carbon
monoxide poisoning, explosion, fire, electric shock, or
other occurrences which may cause injury or property
damage. Consult a qualified installer, service agency, or
the gas supplier for information or assistance. The quali-
fied installer or agency must use only factory-authorized
kits or accessories when modifying this product.
WARNING: Disconnect gas piping from unit when
leak testing at pressure greater than
1
/
2
psig. Pressures
greater than
1
/
2
psig will cause gas valve damage
resulting in hazardous condition. If gas valve is ever
subjected to pressure greater than
1
/
2
psig, it must be
replaced before use. When pressure testing field-
supplied gas piping at pressures of
1
/
2
psig or less, a
unit connected to such piping must be isolated by man-
ually closing the gas valve.
WARNING: Before performing service or mainte-
nance operations on unit, turn off main power switch
to unit and install lockout tag. Electrical shock could
cause personal injury.
installation, start-up and
service instructions
SINGLE PACKAGE ROOFTOP
GAS HEATING/ELECTRIC COOLING UNITS
580D
Sizes 090-150
7
1
/
2
to 12
1
/
2
Tons
Fig. 1 — Typical Unit
Vue de la page 0
1 2 3 4 5 6 ... 47 48

Résumé du contenu

Page 1 - SINGLE PACKAGE ROOFTOP

Cancels: II 580D-90-4 II 580D-90-57/15/00IMPORTANT — READ BEFORE INSTALLING1. Read and become familiar with these installation in-structions before in

Page 2

—10—NOTE: If accessory thru-the-bottom connections areused, refer to the accessory installation instructions forinstallation.High-Voltage Connections

Page 3 - Fig. 3 — Base Unit Dimensions

—11—LEGENDFig. 13 — Field Wiring ConnectionsBM —Blower (Evaporator Fan) MotorLED —Light-Emitting DiodeC—ContactorNEC —National Electrical CodeCAP —Cap

Page 4 - Fig. 4 — Roof Curb Dimensions

—12—Special Procedures for 208-V OperationFor operation on 208 v:Remove black wire with 1/4-in. female spade connector fromthe 230-volt male spade tra

Page 5

—13—Table 3 — Accessory List*See unit wiring book for proper installation instructions.NOTE: Two Time Guard II timers are required.G. Optional Outdoor

Page 6 - Table 1 — Physical Data

—14—Assembly1. Determine if ventilation air is required in building. Ifso, determine the minimum amount to be supplied byeach unit and record quantity

Page 7 - DRAIN PLUG

—15—ECONOMIZERCONTROLBOARDBAROMETRICRELIEFDAMPERECONOMIZERPLUGECONOMIZERMOTORSHIPPINGSCREWBLOCK-OFF PLATEECONOMIZERCONTROL BOARDWIRINGHARNESSBAROMETRI

Page 8

—16—10. Fasten hood top and side plate assembly to outdoor-air opening panel with screws provided.11. Place knob supplied with economizer on OAT. SeeF

Page 9

—17—1. To remove the existing unit filter access panel, raisethe panel and swing the bottom outward. The panel isnow disengaged from the track and can

Page 10

—18—NOTE: Be sure to engage rear EconoMi$er flange under tabsin return air opening of the unit base. See Fig. 37.8. Install the outdoor air block-off

Page 11

—19—OUTDOORAIRSENSORTEMPTEMPCOMOUTPWRBROWNVIOLETWHITEREDBROWNTEMPTEMPCOMOUTPWRRETURNAIRSENSORVIOLETWHITEREDOATCOMOAH-15 VRATCOMRAH+15 VECONOMI$ERCONTR

Page 12

—2—4. Locate the unit where the vent hood will be a mini-mum of 4 ft from openable windows or doors.5. This installation must conform with local build

Page 13

—20—M e c h anica l Coo lin g L o c ko utDetermine the outdoor-air temperature at which you wantthe mechanical cooling (compressors) to be disab

Page 14

—21—Proceed as follows to inspect and prepare the unit for initialstart-up:1. Remove all access panels.2. Read and follow instructions on all WARNING,

Page 15 - Determine — Setting =6

—22—B. Gas InputCheck gas input and manifold pressure in “HIGH FIRE”(W1 and W2 energized at gas valve) after unit start-up (seeTable 6). If adjustment

Page 16 - POSITION

—23—Table 7 — Altitude Compensation**As the height above sea level increases, there is less oxygen percubic foot of air. Therefore, heat input rate sh

Page 17

—24—W1 is energized. The induced-draft motor is energized andthe burner ignition sequence begins. The indoor (evaporator)fan motor (IFM) is energized

Page 18 - Outdoor Air Thermostat

—25—(IFM), compressor no. 1, and condenser fan start. The outdoor(condenser) fan motors (OFM) run continuously while unit iscooling. If the thermostat

Page 19 - DISCONNECT

—26—III. INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTSAdjust evaporator-fan RPM to meet jobsite conditions andtemperature rise in Table 1. Table 8 shows fan

Page 20 - Avoid possible

—27—Table 9 — Motor Data LEGEND*Extensive motor and electrical testing on these units ensures that the full horsepower and watts rangeof the

Page 21

—28—Tabl e 11 — 580D102 Air Delivery, Vertical Discharge UnitsNOTES:1.Boldface indicates a field-supplied drive is required. (See Note 7.)2. indicate

Page 22

—29—Tabl e 13 — 580D150 Air Delivery, Vertical Discharge UnitsNOTES:1.Boldface indicates a field-supplied drive is required. (See Note 8.)2. indicate

Page 23

—3—Fig. 3 — Base Unit DimensionsCONNECTION SIZESA13/8″ Dia [35] Field Power Supply HoleB21/2″ Dia [64] Power Supply KnockoutC13/4″ Dia [44] Charging P

Page 24

—30—Tabl e 15 — 580D102 Air Delivery, Horizontal Discharge UnitsNOTES:1.Boldface indicates a field-supplied drive is required. (See Note 7.)2. indica

Page 25

—31—Tabl e 17 — 580D150 Air Delivery, Horizontal Discharge UnitsNOTES:1.Boldface indicates a field-supplied drive is required. (See Note 8.)2. indica

Page 26

—32—I. AIR FILTERInspect air filters at least once each month, and replace(throwaway-type) or clean (cleanable-type) at least twiceduring each heating

Page 27 - Table 9 — Motor Data

—33—V. REFRIGERANT CHARGEA. Checking and Adjustment Refrigerant ChargeThe refrigerant system is fully charged with R-22 refriger-ant, tested, and fact

Page 28

—34—Fig. 54 — Cooling Charging Chart; 580D090Fig. 55 — Cooling Charging Chart; 580D102

Page 29

—35—CIRCUIT NO. 2CIRCUIT NO. 1Fig. 56 — Cooling Charging Chart; 580D120Fig. 57 — Cooling Charging Chart; 580D150

Page 30

—36—VI. MAIN BURNERSAt the beginning of each heating season, inspect for deterio-ration or blockage due to corrosion or other causes. Observethe main

Page 31

—37—INDUCED-DRAFTMOTORMANIFOLDPRESSURETAPVESTIBULEPLATEFLUE VENTROLLOUTSWITCHBLOWERHOUSINGGAS VALVEBURNERSECTIONFig. 58 — Burner Section Details580D09

Page 32

—38—TROUBLESHOOTINGTable 19 — Cooling Service AnalysisPROBLEM CAUSE REMEDYCompressor andcondenser fan will notstart.Power failure. Call power company.

Page 33

—39—Tabl e 20 — Heating Service AnalysisPROBLEM CAUSE REMEDYBurners will not ignite.Misaligned spark electrodes. Check flame ignition and sensor elect

Page 34

—4—Fig. 4 — Roof Curb Dimensions“B” “C”“D” ALTDRAINHOLE“E”GAS“F”POWER“G”CONTROLCONNECTORPACKAGEACCESSORY2′-87/16″[827]1′-1015/16″[583]13/4″[44.5]3/4″[

Page 35 - CIRCUIT NO. 1

—40—Table 21 — LED Error Code Service AnalysisIMPORTANT: Refer to Table 20 — Heating Service Analysis for addi-tional troubleshooting analysis.

Page 36

—41—Table 22 — Durablade Economizer Service Analysis(Table continued on page 42.)PROBLEM CAUSE REMEDYDamper does not open.Indoor (evaporator) fan is o

Page 37

—42—Tabl e 22 — Durablade Economizer Service Analysis (cont) LEGENDPROBLEM CAUSE REMEDYDamper does not close.Incorrect wiring of e

Page 38 - TROUBLESHOOTING

—43—Table 23 — EconoMi$er Economizer Service Analysis LEGENDPROBLEM CAUSE REMEDYDamper does notopen.Indoor (Evaporator) Fan isOff.

Page 39

—44—LEGEND FOR FIG. 60IMPORTANT: Refer to unit wiring label for actual unit wiring information.AHA —Adjustable Heat AnticipatorBR —Blower RelayC —Cont

Page 40 - WARNING:

—45—NOTES:1. If any of the original wire furnished must bereplaced, it must be replaced with Type 90 Cwire or its equivalent.2. Three-phase motors are

Page 41

Copyright 2000 Bryant Heating & Cooling Systems CATALOG NO. 5358-005

Page 43

Copyright 2000 Bryant Heating & Cooling SystemsCL-1CATALOG NO. 5358-005CUT ALONG DOTTED LINECUT ALONG DOTTED LINESTART-UP CHECKLIST(Remove and Use

Page 44 - LEGEND FOR FIG. 60

—5—II. UNIT DUCT CONNECTIONSOn vertical units, secure all ducts to roof curb and buildingstructure. Do not connect ductwork to unit. On horizontaluni

Page 45

—6—Table 1 — Physical Data LEGENDBhp — Brake Horsepower*Weight of 14-in. roof curb. †Rollout switch is manual reset.**Indicates a FIOP (Factor

Page 46

—7—IV. FIELD CONNECTIONSA. External Trap Condensate DrainThe unit’s 3/4-in. condensate drain connections are locatedon the bottom and side of the unit

Page 47

—8—5. Install an accessible, external, manual main shutoffvalve in gas supply pipe within 6 ft of heating section. 6. Install ground-joint union close

Page 48 - III. START-UP:

—9—Contact your LP gas supplier or regulator manufacturer forfurther details regarding tank sizing, recommended regula-tor settings, and pipe sizing.S

Commentaires sur ces manuels

Pas de commentaire