Fieldbus ECO-Coupler 750-343 61
Configuration
WAGO-I/O-SYSTEM 750
PROFIBUS
3.1.5.2 Identification Bytes
The identification bytes contain information about the design and structure of
the module inputs and outputs. For the configuration, each I/O module, or
each channel is allocated an identification (module).
Bit Meaning
7 6 5 4 3 2 1 0
0
0
0
...
1
0
0
0
...
1
0
0
1
...
1
0
1
0
...
1
Data length
1 byte or word
2 bytes or words
3 bytes or words
...
16 bytes or words
0
0
1
1
0
1
0
1
Input and output
spec. identification formats
Input
Output
Input and output
0
1
Format
0 = Byte structure
1 = Word structure
0
1
Consistence over
Byte or word
Total length
This information is saved in the GSD file. During configuring the I/O module
is selected in accordance with the article number using the configuration
software in the hardware cataloge.
Modules are compiled in the table to make things simpler.
Module Description Example
Module Configuration of I/O modules 750-400 2 DI/24 V DC/3.0 ms
*-Module Configuration of digital I/O modules.
Binary data is mapped to a byte that
has already been started by “Module”.
*750-400 2 DI/24 V DC/3.0 ms