©2014 Twin City Fan Companies, Ltd.Receiving, Inspection & UnpackingGeneral InstallationWhen the equipment is received all items should be careful
10 Twin City IM-4050Dimensions and WeightsModels DCRU/DCRURMODELDAMPERSIZECANTEDCURB SIZESELF FLASHCURB SIZEBCRU BCRUR110B 110B18 x 18 221⁄2 x 221⁄2
Twin City IM-4050 11Models DCRW/DCRWRMOUNTING BRACKET HOLE MOUNTING PATTERN 5/16" ANCHOR STUD (8) 6.78 6.78 D SQUARE A DIA. 2.00 MOUNTING BRACKE
12 Twin City IM-4050Model DCLHBDAE SQUAREC2.00Dimensions and WeightsModel BCLHCBADF2.00 TYPE SQUARESIZEAMAX.B C DE SQ.CANTEDCURBDAMPERSIZEAVG. SHIP W
Twin City IM-4050 13Model DCLPE SQUARECB2.00 TYPADimensions and WeightsModel BCLPE SQUARE2.00 TYPBADCSIZEAMAX.B CE SQ.CANTEDCURBDAMPERSIZEAVG. SHIP W
14 Twin City IM-4050Seller warrants to the original purchaser that the goods sold hereunder shall be free from defects in workman-ship and material u
Twin City IM-4050 15Refer to pages 6 and 7 for recommended maintenance.
5MWG10/14TWIN CITY FAN & BLOWER | WWW.TCF.COM5959 Trenton Lane N | Minneapolis, MN 55442 | Phone: 763-551-7600 | Fax: 763-551-7601
2 Twin City IM-4050Wall Fan Installation 1. Your wall fan is shipped with a wall mounting brack-et. Refer to the wall fan dimensional drawing
Twin City IM-4050 3Roof Fan InstallationDownblast Fans: 1. Position the fan with its wiring conduit in line with the wiring coming up through t
4 Twin City IM-4050Figure 3. Low End Setpoint AdjustmentNOTE: 5 amp model shown. On 10 and 15 amp models, adjustment is made through clear-ance hole
Twin City IM-4050 5Figure 4. Eliminate Slack Figure 5. Belt DeflectionFigure 6. Alignment Figure 7. Two-Groove Sheaves (Pulleys)Figure 8. BeltsDefl
6 Twin City IM-4050Three-Pulley (Idler Sheave) AssemblySingle bolt belt adjustment (Figure 9) can be made by loosening the idler sheave bolt (with 3/
Twin City IM-4050 7OIL TUBESFigure 10. Sleeve Bearing Motor Oil Tube LocationStorageIf fans are stored for any length of time, they should be stored
8 Twin City IM-4050Fan Troubleshooting Chart PROBLEM POSSIBLE CAUSES FAN DOES NOT OPERATE 1. Wrong voltage. 2. Electricity turned off or
Twin City IM-4050 9Dimensions and WeightsModel DCRDModel BCRD-EModel BCRDA DIA.BC2.00"E SQUAREROOF OPENING(DAMPER SIZE + 0.50 INCHES)CURB SIZE